IS200SPROH1ACC

Brand: GE Fanuc
Order Number: IS200SPROH1ACC
Type: Mark VIe Backup Protection Terminal Board
Country:
Low stock: 12 left

Description

Caret Down

The GE IS200SPROH1ACC is a backup protection terminal board designed for the GE Mark VIe turbine control system. It provides signal termination and interfacing for the PPRO I/O pack, including turbine speed inputs, generator voltage sensing, and bus voltage sensing. Its onboard potential transformers (PTs) provide isolated voltage signals for synchronization-related measurements, while a dedicated connector supports interfacing with the backup trip relay terminal board.

Functional Description

The IS200SPROH1ACC provides the electrical interface between field signals and the associated Mark VIe protection hardware. It combines speed-signal termination with generator and bus voltage sensing, allowing the connected PPRO I/O pack to receive signals required by the backup protection arrangement.

Two onboard single-phase potential transformers provide voltage sensing for generator and bus inputs. Their nominal secondary output is 115 V rms, with a specified synchronization voltage range of 75-130 V rms. The magnetic isolation barrier separates the PT input circuits from the associated measurement circuitry.

PPRO Interface and Signal Connections

The board provides a dedicated JA1 connection for the PPRO I/O pack and a JA3 interface for the backup trip terminal board cable. The DC-37 connector is identified as the cable interface for the backup relay terminal board.

The documented terminal assignments are:

Terminal or Connector Function
Terminals 1-4 Potential transformer inputs
Terminals 5-6 No board connection
Terminals 7-15 Reserved control connections routed to JA1
Terminals 16-18 No board connection
Terminals 19-24 Speed inputs
JA1 PPRO I/O pack connection
JA3 Backup trip terminal board cable connection
DC-37 Backup trip relay terminal board cable interface

These assignments should be checked against the installed board revision and the applicable system wiring drawings before field wiring or replacement.

Technical Specifications

Parameter Specification
Model IS200SPROH1ACC
Brand General Electric (GE)
Series Mark VIe
Product Type Backup Protection Terminal Board
Associated I/O Pack PPRO
Voltage Sensing 2 single-phase potential transformers
PT Secondary Output 115 V rms nominal
PT Input Loading Less than 3 VA per input
Synchronization Voltage Range 75-130 V rms
PT Magnetic Isolation 1,500 V rms
Maximum Stated Cable Length 1,000 ft
Stated Cable Size 18 AWG
Operating Temperature -30 to 65 deg C
Dimensions 15.9 cm high x 17.8 cm wide
Technology Surface-mount

Generator and Bus Synchronization

The two PT circuits provide generator and bus voltage measurements for the backup synchronization function. The PPRO protection hardware uses these voltage signals to evaluate synchronization conditions, including voltage and phase relationships, before a generator breaker closing permissive is issued.

The specified PT input loading of less than 3 VA per input defines the measurement circuit loading requirement. The 1,500 V rms magnetic isolation barrier provides electrical separation between the PT input circuits and the associated measurement electronics.

Field Wiring Considerations

The supplied product specifications identify 18 AWG cable and a maximum stated cable length of 1,000 ft for the voltage sensing connections. Cable routing, shielding, terminal assignments, and actual installation limits should be checked against the applicable Mark VIe control drawings.

The JA1 PPRO interface and DC-37 backup trip connection must also match the installed protection configuration. Verify the complete board part number before replacing an existing terminal board.

Frequently Asked Questions

Q: What is the primary function of the GE IS200SPROH1ACC?

A: It provides signal termination and interfacing for a Mark VIe backup protection arrangement. Its functions include turbine speed signal connections, generator and bus voltage sensing, and connection to the backup trip terminal board.

Q: Does the IS200SPROH1ACC support generator synchronization monitoring?

A: Yes. Its two onboard potential transformers provide generator and bus voltage signals for the associated PPRO synchronization monitoring function. The nominal PT secondary output is 115 V rms, with a specified synchronization voltage range of 75-130 V rms.

Q: What should be checked before replacing this board?

A: Check the complete part number, PPRO interface, DC-37 trip connection, PT wiring, and terminal assignments. Do not assume that another SPROH1A revision or a similarly numbered terminal board has an identical configuration.