FTA-T-16
Description
Description
Overview
The FTA-T-16 is a Honeywell Fail-Safe Active Digital Input module with line-monitoring, designed for 16-channel industrial control applications.
Power & Input
-
Number of Input Channels: 16
-
Power Requirement: 30 VDC, 150 mA (all inputs closed)
-
Max Current per Channel: <12 mA at 30 VDC
Signal Output
-
To Passive Transmitters (Vext): Open voltage typically 24 VDC
-
To 10105/2/1 Module: Output voltage 0 to 3.5 VDC
Module Layout
-
Dimensions: 110 × 70 × 60 mm (4.33 × 2.76 × 2.36 in)
-
DIN Rail: TS32 / TS35 × 7.5 mm, used rail length 111 mm (4.37 in)
-
Termination: Screw terminals
-
Max Wire Diameter: 2.5 mm² (AWG 14)
-
Strip Length: 7 mm (0.28 in)
-
Tightening Torque: 0.5 Nm (0.37 ft-lb)
Field Wiring Limits
-
Wire Resistance: <500 Ω
-
Device Resistance: RA 1 kΩ ±10%, RB 3.3 kΩ / 10 kΩ ±10%
-
Hydrogen Loops (A & B): Max Inductance 500 mH, Max Capacitance 0.3 µF
-
Non-Hydrogen Loops (C & D): Max Inductance 1 H, Max Capacitance 7 µF