FAU800
Description
Description
Overview
FAU800 Flame Analysis Unit designed for monitoring flame characteristics with configurable relay settings, dual analog outputs, and redundant serial communication interfaces.
Relay Configuration
-
Flame Failure Relay Drop-Out: Configurable from 0.1 to 2.5 seconds
-
Flame Relay(s): Three total, each with Form C contacts
-
Flame Relay Contact Ratings: 250 Vac, 3A, 750 VA; 220 Vdc, 300 mA, 66 W
-
Fault Relay Contact Ratings: 250 Vac, 3A, 750 VA; 220 Vdc, 300 mA, 66 W
Signal Outputs
-
Analog Flame Signal Outputs: Two channels, 4-20 mA each
-
Monitoring Options: Intensity, Frequency, Quality, AC Amplitude (independent per channel)
Communication Interfaces
-
Serial Data Communication: Two galvanically isolated RS-485 interfaces
-
Data Format: MODBUS (default), PROFIBUS (optional)
Self-Check Function
-
Electronics Check Interval: Every 0.1 seconds
Environmental Conditions
-
Ambient Temperature: 0° to 60°C
-
Humidity: Up to 95% non-condensing
Physical Specifications
-
Dimensions: Height 13 cm, Length 12 cm, Width 11 cm
-
Electrical Connections: Screw terminals, compression type, 12–20 AWG wires
-
Mounting: DIN rail mounted
Power Requirements
-
Consumption: 4 W (min), 10 W (max), 6 W (typical)
Stacking Limitations
-
With End Module Power Entry: Up to 4 modules
-
With Middle Module Power Entry: Up to 7 modules
Tags:
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews


Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.