Caret Down

Overview

TU842 is a redundant horizontal MTU supporting up to 16 I/O channels with dual power and ModuleBus connections.

Electrical Specifications

  • Rated voltage (insulation): 50 V

  • Dielectric test voltage: 500 V AC

  • Max continuous current per I/O channel: 3 A

  • Max continuous current per process voltage (L+): 10 A

  • ModuleBus 5 V current distribution: 1.5 A

  • ModuleBus 24 V current distribution: 1.5 A

Connectivity

  • Process connections: 56 terminals

  • Supported I/O channels: Up to 16 (2 terminals per channel)

  • Process power terminals: 4 (L+), 20 (0 V)

Wiring and Installation

  • Solid wire size: 0.2 – 4 mm²

  • Stranded wire size: 0.2 – 2.5 mm² (24 – 12 AWG)

  • Recommended torque: 0.5 – 0.6 Nm

  • Stripping length: 7 mm

Mechanical Design

  • Width: 131 mm (with connector) / 124 mm (installed)

  • Depth: 64 mm (including terminals)

  • Height: 186.5 mm (including locking device)

  • Weight: 0.6 kg

  • Mechanical keying: 2+2 keys, 36 combinations

  • I/O module lock: Included

Standards and Protection

  • Equipment class: Class I (IEC 61140, earth protected)

  • Protection rating: IP20 (IEC 60529)