900B16-0001
Description
Description
Overview
The 900B16-0001 is a Honeywell HC900 analog output module with 16 isolated outputs arranged in four groups.
Output Details
-
Channels: 16 outputs, isolated in 4 groups of 4
-
Current Range: 0 to 21.0 mA, selectable
-
Load Resistance: Up to 750 ohms
-
Galvanic Isolation:
-
500 VDC between groups
-
500 VDC from logic
Performance
-
Accuracy: 0.1% full scale at reference conditions
-
Minimum Sensing Current: > 0.5 mA per output
-
D/A Resolution: 13+ bits (1 part in 13,332)
Calibration & Diagnostics
-
Calibration Data: Stored in non-volatile memory with factory redundancy
-
Field Calibration: Individual channel adjustment available
-
Diagnostics: Monitors factory calibration, field calibration, and configuration
-
Output Verification: Feedback to controller confirming output current flow
Power Requirements
-
5 V Supply: 350 mA max
-
24 V Supply: 700 mA max
Installation Limitations
-
Modules per Rack: Maximum of 2 when powered from internal 24 V backplane
Product Benefits