745-W2-P5-G5-HI-R-E
Description
Description
Overview
745-W2-P5-G5-HI-R-E is a GE Multilin transformer protection relay designed for two- or three-winding transformers with advanced differential protection.
Applicability
-
Transformers: Two-winding or three-winding
-
Frequency: 50 or 60 Hz nominal
-
Frequency tracking: 40–65 Hz (current ≤ 1 × CT), 5–65 Hz (current > 1 × CT), 2–65 Hz (voltage sensing enabled)
Control Power
-
Options: LO/HI (specified when ordering)
-
LO range: 20–60 V DC; 20–48 V AC
-
HI range: 90–300 V DC; 70–265 V AC
-
Power: 30 VA nominal, 40 VA max
-
Ride-through time: 16.7 ms at 0% control power
-
Fuse rating: 3.15 A
-
Fuse type: 5 × 20 mm slow-blow Littelfuse
Protection Elements
-
Operating current pickup: 0.05–1.00 × CT
-
Dropout level: 97–98% of pickup
-
Slope 1 range: 15–100%
-
Slope 2 range: 50–100%
-
Kneepoint (KP): 1.0–20.0 × CT
-
Harmonic restraint: 0.1–65%
-
Operate time (solid state): 26–52 ms depending on pickup
-
Relay outputs 2–5 time: 30–56 ms depending on pickup