140CPU31110
Description
Description
Product overview
-
Model: 140CPU31110
-
Brand: Schneider Electric
-
Type: Unity Processor Module for Modicon Quantum Platform
General Information
-
Platform: Modicon Quantum
-
Clock frequency: 66 MHz
-
Internal memory: 548 kB RAM
-
Bus current: 1800 mA
I/O Capabilities
-
Local discrete I/O: Unlimited (max 27 slots)
-
Remote discrete I/O: 31,744 inputs and 31,744 outputs via S908
-
Distributed discrete I/O: 8,000 inputs and 8,000 outputs per Modbus Plus network
-
Local analog I/O: Unlimited (max 27 slots)
-
Distributed analog I/O: 500 inputs and 500 outputs per Modbus Plus network
-
Remote analog I/O: 1,984 inputs and 1,984 outputs via S908
-
Application-specific I/O: Includes high-speed interrupt, counter, accurate time stamping, serial link
Communication & Connectivity
-
Integrated ports:
– 1 Modbus Plus
– 2 Modbus RS232/485 -
Optional module support:
– Ethernet
– Modbus
– Modbus Plus
– Profibus DP
– Sy/Max -
Max connections:
– 2 Ethernet TCP/IP (local)
– 2 Modbus Plus (local)
– 2 Modbus (RS232/485)
– 2 AS-Interface (distributed)
– 4 AS-Interface (remote)
– 2 Profibus DP (local) -
Connection types:
– 1 SUB-D 9 (Modbus Plus)
– 2 SUB-D 9 (Modbus)
Rack & Slot Support
-
Number of slots: 16 total
-
Rack configuration:
– 2 local racks
– 63 distributed I/O stations (Modbus Plus)
– 31 remote I/O stations (S908)
– 0 Ethernet remote I/O
Application & Performance
-
Application tasks:
– 1 cyclic/periodic master task
– 1 fast periodic task
– 16 timer interrupt tasks
– 64 I/O interrupt tasks
– 64 interrupt tasks -
Execution speed:
– 0.1–0.27 µs (floating/fixed-point)
– 0.12–0.585 µs (Boolean/word) -
Instruction throughput:
– 1.86 Kinst/ms (100% Boolean)
– 2.49 Kinst/ms (65% Boolean, 35% numerical) -
System overhead:
– 0.2 ms (fast task)
– 1 ms (master task)
Indicators & Diagnostics
-
RUN (green): CPU solving logic
-
READY (green): Passed diagnostics
-
Modbus/Modbus Plus Comm (green): Active communication
-
Memory port (orange): Write protection active
-
BAT LOW (red): Low or missing battery
-
ERROR A (red): Modbus Plus error
Configuration Features
-
Memory port switch: ON/OFF
-
Comm port switch: ASCII/RTU/Memory
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews



Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.