9905-976
Beschreibung
Beschreibung
Overview
-
Model Number : 9905-976
-
Type : ProTech 203 Overspeed Protection System
-
Manufacturer : Woodward
Electrical & Power Details
-
Input Voltage :
-
120 Vac/dc = 88–132 Vac, 90–150 Vdc
-
Power Consumption :
-
7.25 W
Operational Features
-
Speed Calculation :
-
Three individual speed calculations
-
Two-out-of-three hardware vote for overspeed detection
-
Response Time :
-
40 ms maximum
-
Trip Relay Activation :
-
Activated if two of three units detect overspeed
-
Operator Interface :
-
1 Keypad and Display per Module
Configuration & Parameters
-
Trip Speed Set Point :
-
250 rpm minimum, 25,000 rpm maximum
-
MPU Fail Set Point :
-
100 rpm minimum, 25,000 rpm maximum
Environmental Conditions
-
Operating Temperature :
-
–25 to +60 °C
Dimensions
-
Size :
-
W: 482.6 mm x H: 310.4 mm x D:
System Design
-
Modular Design :
-
Units A, B, and C are identical with independent programming
-
CPU Fail Indication :
-
Included as part of the safety features