{"product_id":"yokogawa-anb10d-223-s2-esb-bus-node-unit","title":"Yokogawa ANB10D-223 S2 ESB Bus Node Unit","description":"\u003cp\u003eThe \u003cstrong\u003eYokogawa ANB10D-223 S2\u003c\/strong\u003e is identified by its ANB10D model designation as a dual-redundant ESB Bus Node Unit for the Yokogawa Fieldbus I\/O (FIO) system. It provides the interface between a Field Control Unit (FCU) and installed I\/O modules, transferring field analog and contact signals through the ESB bus while distributing power to the I\/O modules. The exact ordering suffix configuration requires separate verification.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eFunctional Description\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe ANB10D is a local node connected directly to an FCU through the ESB bus. It provides the node-level interface for communication between the controller and the installed I\/O modules.\u003c\/p\u003e\n\u003cp\u003eIts main functions include:\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eTransferring analog and contact I\/O signals between the field-side I\/O modules and the FCU.\u003c\/li\u003e\n\u003cli\u003eDistributing power to installed I\/O modules.\u003c\/li\u003e\n\u003cli\u003eSupporting a dual-redundant ESB bus node architecture.\u003c\/li\u003e\n\u003cli\u003eAccommodating power supply modules, ESB bus interface modules and I\/O modules within the node assembly.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003eHardware Configuration\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe node unit uses a modular internal arrangement consisting of power supply modules, ESB bus interface slave modules and I\/O modules.\u003c\/p\u003e\n\u003cp\u003eFor the ANB10D dual-redundant architecture, the documented configuration includes:\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eTwo power supply modules for dual-redundant power supply operation.\u003c\/li\u003e\n\u003cli\u003eTwo SB401 ESB Bus Interface Slave Modules.\u003c\/li\u003e\n\u003cli\u003eUp to 8 I\/O module positions.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eThe power supply modules distribute power to the I\/O modules and field transmitters. The dual-module arrangement provides redundant power supply architecture at the node level.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eInstallation and Environmental Conditions\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe ANB10D is designed for installation in a 19-inch equipment rack, using four M5 mounting screws. Its documented external dimensions are 482.6 x 221.5 x 205 mm.\u003c\/p\u003e\n\u003cp\u003eThe general specifications for the ANB10D specify an operating ambient temperature range of 0 to 60 deg C under standard conditions. Actual installation limits may depend on the cabinet arrangement and installed I\/O modules.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eTechnical Specifications\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eANB10D-223 S2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eYokogawa\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eDual-Redundant ESB Bus Node Unit\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem\u003c\/td\u003e\n\u003ctd\u003eFieldbus I\/O (FIO)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommunication Bus\u003c\/td\u003e\n\u003ctd\u003eESB Bus\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNode Configuration\u003c\/td\u003e\n\u003ctd\u003eDual-redundant\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Supply Architecture\u003c\/td\u003e\n\u003ctd\u003eDual power supply modules\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBus Interface\u003c\/td\u003e\n\u003ctd\u003eSB401 ESB Bus Interface Slave Modules\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum I\/O Module Positions\u003c\/td\u003e\n\u003ctd\u003e8\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting\u003c\/td\u003e\n\u003ctd\u003e19-inch rack mounting\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting Screws\u003c\/td\u003e\n\u003ctd\u003e4 x M5\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e482.6 x 221.5 x 205 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e0 to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e10 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003e\u003cstrong\u003eFrequently Asked Questions\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What is the difference between ANB10D and ANB10S?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: ANB10D is the node unit for a dual-redundant ESB bus configuration, whereas ANB10S is designed for a single ESB bus configuration. Their node architecture and ordering configurations are different.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: How many I\/O modules can the ANB10D accommodate?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The documented configuration supports up to 8 I\/O modules. Actual module allocation and installation restrictions depend on the selected I\/O modules and system configuration.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Does ANB10D-223 S2 specify a particular power supply voltage?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The general ANB10D ordering documentation identifies 100-120 V AC, 220-240 V AC and 24 V DC power supply options. However, the exact meaning of the supplied -223 S2 designation could not be verified against the published ordering-code structure. The nameplate should be checked before selecting a replacement.\u003c\/p\u003e","brand":"Yokogawa","offers":[{"title":"Default Title","offer_id":69399915987186,"sku":"ANB10D-223 S2","price":245.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0730\/5589\/5794\/files\/ANB10D-420CU2NNDEL_1.jpg?v=1740981795","url":"https:\/\/www.petrospare.com\/products\/yokogawa-anb10d-223-s2-esb-bus-node-unit","provider":"Petro Spare Industrial Limited","version":"1.0","type":"link"}