{"product_id":"yokogawa-adv151-p60-b5s00-digital-input-module","title":"Yokogawa ADV151-P60\/B5S00 Digital Input Module","description":"\u003cp\u003eThe Yokogawa ADV151-P60\/B5S00 is a 32-channel isolated digital input module designed to receive 24 V DC discrete signals from field devices. It supports pushbutton input and includes a status display. The \/B5S00 configuration specifies a pressure clamp terminal block (ATB5S-00), providing a direct terminal connection option for field signal wiring.\u003c\/p\u003e\n\u003ch3\u003eFunctional Description\u003c\/h3\u003e\n\u003cp\u003eThe ADV151 receives binary signals from external devices and transfers their ON\/OFF states to the control system. Its 32 isolated input channels allow multiple field signals to be monitored through one module.\u003c\/p\u003e\n\u003cp\u003eThe -P configuration provides pushbutton input functionality, while the -P60 model configuration includes a status display. The module is specified for 24 V DC sink\/source input signals, allowing it to interface with supported field contact and switching circuits.\u003c\/p\u003e\n\u003ch3\u003eInput Specifications\u003c\/h3\u003e\n\u003cp\u003eThe module accepts 24 V DC ON\/OFF signals in either sink or source configuration. The input threshold specifications distinguish valid ON and OFF states, while the 30.0 V DC maximum allowable input voltage defines the upper electrical limit.\u003c\/p\u003e\n\u003cp\u003eThe input response time is 8 ms or less for status input. For pushbutton input, the minimum ON detection time is 20 ms, with a maximum ON\/OFF cycle of 25 Hz. These timing limits should be considered when configuring pulse or contact signals.\u003c\/p\u003e\n\u003ch3\u003eTerminal Connection and Isolation\u003c\/h3\u003e\n\u003cp\u003eThe \/B5S00 option provides the ATB5S-00 pressure clamp terminal block for digital input connections. This configuration is intended for direct field wiring through the specified terminal block rather than the alternative KS cable interface.\u003c\/p\u003e\n\u003cp\u003eThe input-to-system withstand voltage is 2 kV AC for 1 minute. The common-to-common withstand voltage is 500 V AC for 1 minute, with a common shared by every 16 channels. All 24 V DC input signals connected to the module must have the same polarity within each 16-channel common group.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eADV151-P60\/B5S00\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eYokogawa\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eDigital Input Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Input Channels\u003c\/td\u003e\n\u003ctd\u003e32\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Input Voltage\u003c\/td\u003e\n\u003ctd\u003e24 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Configuration\u003c\/td\u003e\n\u003ctd\u003eSink \/ Source\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput ON Voltage\u003c\/td\u003e\n\u003ctd\u003e18 to 26.4 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput OFF Voltage\u003c\/td\u003e\n\u003ctd\u003e5.0 V DC or less\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Current\u003c\/td\u003e\n\u003ctd\u003e4.1 mA +\/- 20% per channel\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Allowable Input Voltage\u003c\/td\u003e\n\u003ctd\u003e30.0 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Response Time\u003c\/td\u003e\n\u003ctd\u003e8 ms or less (status input)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMinimum ON Detection Time\u003c\/td\u003e\n\u003ctd\u003e20 ms (pushbutton input)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum ON\/OFF Cycle\u003c\/td\u003e\n\u003ctd\u003e25 Hz (pushbutton input)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput-to-System Withstand Voltage\u003c\/td\u003e\n\u003ctd\u003e2 kV AC, 1 minute\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommon-to-Common Withstand Voltage\u003c\/td\u003e\n\u003ctd\u003e500 V AC, 1 minute\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Current Consumption\u003c\/td\u003e\n\u003ctd\u003e500 mA at 5 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStatus Display\u003c\/td\u003e\n\u003ctd\u003eIncluded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTerminal Connection\u003c\/td\u003e\n\u003ctd\u003eATB5S-00 Pressure Clamp Terminal Block\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.30 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eModel Configuration\u003c\/h3\u003e\n\u003cp\u003eThe ordering code identifies the module's input function, display configuration and terminal connection.\u003c\/p\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eCode\u003c\/th\u003e\n\u003cth\u003eDescription\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eADV151\u003c\/td\u003e\n\u003ctd\u003e32-channel, 24 V DC isolated digital input module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e-P\u003c\/td\u003e\n\u003ctd\u003eWith pushbutton input\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e6\u003c\/td\u003e\n\u003ctd\u003eWith status display; without explosion protection\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e0\u003c\/td\u003e\n\u003ctd\u003eBasic type\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\/B5S00\u003c\/td\u003e\n\u003ctd\u003ePressure clamp terminal block for digital input, ATB5S-00\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003eThe complete ordering number ADV151-P60\/B5S00 therefore identifies the pushbutton-input version with status display and the specified pressure clamp terminal block. The -P60 configuration does not indicate explosion protection.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How many digital input signals can the ADV151-P60\/B5S00 handle?\u003c\/p\u003e\n\u003cp\u003eA: It supports 32 isolated digital input channels. Each channel accepts 24 V DC sink\/source signals within the specified input voltage thresholds.\u003c\/p\u003e\n\u003cp\u003eQ: What is the function of the B5S00 option?\u003c\/p\u003e\n\u003cp\u003eA: The \/B5S00 option specifies the ATB5S-00 pressure clamp terminal block for field wiring. It distinguishes this configuration from versions using dedicated cables or MIL connector interfaces.\u003c\/p\u003e\n\u003cp\u003eQ: Does the ADV151-P60\/B5S00 support pushbutton inputs?\u003c\/p\u003e\n\u003cp\u003eA: Yes. The -P suffix identifies the pushbutton input function. The module supports pushbutton edge counting, with a minimum ON detection time of 20 ms and a maximum ON\/OFF cycle of 25 Hz.\u003c\/p\u003e","brand":"Yokogawa","offers":[{"title":"Default Title","offer_id":69284420255986,"sku":"ADV151-P60\/B5S00","price":235.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0730\/5589\/5794\/files\/ADV151-P60B5S00.jpg?v=1794378224","url":"https:\/\/www.petrospare.com\/products\/yokogawa-adv151-p60-b5s00-digital-input-module","provider":"Petro Spare Industrial Limited","version":"1.0","type":"link"}