{"product_id":"ge-is200sproh1acc-mark-vie-backup-protection-terminal-board","title":"GE IS200SPROH1ACC Mark VIe Backup Protection Terminal Board","description":"\u003cp\u003eThe \u003cstrong\u003eGE IS200SPROH1ACC\u003c\/strong\u003e is a backup protection terminal board designed for the GE Mark VIe turbine control system. It provides signal termination and interfacing for the PPRO I\/O pack, including turbine speed inputs, generator voltage sensing, and bus voltage sensing. Its onboard potential transformers (PTs) provide isolated voltage signals for synchronization-related measurements, while a dedicated connector supports interfacing with the backup trip relay terminal board.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eFunctional Description\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe IS200SPROH1ACC provides the electrical interface between field signals and the associated Mark VIe protection hardware. It combines speed-signal termination with generator and bus voltage sensing, allowing the connected PPRO I\/O pack to receive signals required by the backup protection arrangement.\u003c\/p\u003e\n\u003cp\u003eTwo onboard single-phase potential transformers provide voltage sensing for generator and bus inputs. Their nominal secondary output is 115 V rms, with a specified synchronization voltage range of 75-130 V rms. The magnetic isolation barrier separates the PT input circuits from the associated measurement circuitry.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003ePPRO Interface and Signal Connections\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe board provides a dedicated JA1 connection for the PPRO I\/O pack and a JA3 interface for the backup trip terminal board cable. The DC-37 connector is identified as the cable interface for the backup relay terminal board.\u003c\/p\u003e\n\u003cp\u003eThe documented terminal assignments are:\u003c\/p\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eTerminal or Connector\u003c\/th\u003e\n\u003cth\u003eFunction\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eTerminals 1-4\u003c\/td\u003e\n\u003ctd\u003ePotential transformer inputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTerminals 5-6\u003c\/td\u003e\n\u003ctd\u003eNo board connection\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTerminals 7-15\u003c\/td\u003e\n\u003ctd\u003eReserved control connections routed to JA1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTerminals 16-18\u003c\/td\u003e\n\u003ctd\u003eNo board connection\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTerminals 19-24\u003c\/td\u003e\n\u003ctd\u003eSpeed inputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eJA1\u003c\/td\u003e\n\u003ctd\u003ePPRO I\/O pack connection\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eJA3\u003c\/td\u003e\n\u003ctd\u003eBackup trip terminal board cable connection\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDC-37\u003c\/td\u003e\n\u003ctd\u003eBackup trip relay terminal board cable interface\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003eThese assignments should be checked against the installed board revision and the applicable system wiring drawings before field wiring or replacement.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eTechnical Specifications\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eIS200SPROH1ACC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGeneral Electric (GE)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSeries\u003c\/td\u003e\n\u003ctd\u003eMark VIe\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eBackup Protection Terminal Board\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAssociated I\/O Pack\u003c\/td\u003e\n\u003ctd\u003ePPRO\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVoltage Sensing\u003c\/td\u003e\n\u003ctd\u003e2 single-phase potential transformers\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePT Secondary Output\u003c\/td\u003e\n\u003ctd\u003e115 V rms nominal\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePT Input Loading\u003c\/td\u003e\n\u003ctd\u003eLess than 3 VA per input\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSynchronization Voltage Range\u003c\/td\u003e\n\u003ctd\u003e75-130 V rms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePT Magnetic Isolation\u003c\/td\u003e\n\u003ctd\u003e1,500 V rms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Stated Cable Length\u003c\/td\u003e\n\u003ctd\u003e1,000 ft\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStated Cable Size\u003c\/td\u003e\n\u003ctd\u003e18 AWG\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e-30 to 65 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e15.9 cm high x 17.8 cm wide\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTechnology\u003c\/td\u003e\n\u003ctd\u003eSurface-mount\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003e\u003cstrong\u003eGenerator and Bus Synchronization\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe two PT circuits provide generator and bus voltage measurements for the backup synchronization function. The PPRO protection hardware uses these voltage signals to evaluate synchronization conditions, including voltage and phase relationships, before a generator breaker closing permissive is issued.\u003c\/p\u003e\n\u003cp\u003eThe specified PT input loading of less than 3 VA per input defines the measurement circuit loading requirement. The 1,500 V rms magnetic isolation barrier provides electrical separation between the PT input circuits and the associated measurement electronics.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eField Wiring Considerations\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe supplied product specifications identify 18 AWG cable and a maximum stated cable length of 1,000 ft for the voltage sensing connections. Cable routing, shielding, terminal assignments, and actual installation limits should be checked against the applicable Mark VIe control drawings.\u003c\/p\u003e\n\u003cp\u003eThe JA1 PPRO interface and DC-37 backup trip connection must also match the installed protection configuration. Verify the complete board part number before replacing an existing terminal board.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eFrequently Asked Questions\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What is the primary function of the GE IS200SPROH1ACC?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: It provides signal termination and interfacing for a Mark VIe backup protection arrangement. Its functions include turbine speed signal connections, generator and bus voltage sensing, and connection to the backup trip terminal board.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Does the IS200SPROH1ACC support generator synchronization monitoring?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: Yes. Its two onboard potential transformers provide generator and bus voltage signals for the associated PPRO synchronization monitoring function. The nominal PT secondary output is 115 V rms, with a specified synchronization voltage range of 75-130 V rms.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What should be checked before replacing this board?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: Check the complete part number, PPRO interface, DC-37 trip connection, PT wiring, and terminal assignments. Do not assume that another SPROH1A revision or a similarly numbered terminal board has an identical configuration.\u003c\/p\u003e","brand":"GE Fanuc","offers":[{"title":"Default Title","offer_id":69480941682930,"sku":"IS200SPROH1ACC","price":352.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0730\/5589\/5794\/files\/IS200SPROH1ACC.jpg?v=1795587268","url":"https:\/\/www.petrospare.com\/products\/ge-is200sproh1acc-mark-vie-backup-protection-terminal-board","provider":"Petro Spare Industrial Limited","version":"1.0","type":"link"}