{"product_id":"ge-ic200alg320e-versamax-analog-current-output-module","title":"GE IC200ALG320E VersaMax Analog Current Output Module","description":"\u003cp\u003eThe \u003cstrong\u003eGE IC200ALG320E\u003c\/strong\u003e is a four-channel analog current output module in the VersaMax I\/O series. It provides four single-ended, current-sourcing outputs with a 4-20 mA signal range for controlling external field devices. The module features 12-bit analog conversion, 4 uA output resolution, a maximum update rate of 0.3 ms, and configurable output behavior for interrupted communications or controller stops.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eFunctional Description\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe IC200ALG320E converts digital output values received through the VersaMax backplane into proportional 4-20 mA current signals. Each of its four output channels operates as a single-ended current source, allowing the controller to regulate external devices through analog current references.\u003c\/p\u003e\n\u003cp\u003eThe 4-20 mA signal range supports standard industrial control loops. The 12-bit resolution provides fine output adjustment, while the 0.3 ms maximum update rate defines the module's specified output update interval.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eOutput Configuration and Diagnostics\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe four outputs belong to a single group and share the external field-side power arrangement. The module supports two configurable output behaviors: holding the last output state or returning the outputs to 4 mA. The selected behavior determines how the field outputs respond to specified interruption conditions.\u003c\/p\u003e\n\u003cp\u003eTwo LED indicators provide local status information:\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eFLD PWR:\u003c\/strong\u003e Indicates the presence of field-side power for the analog output circuits.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOK:\u003c\/strong\u003e Indicates that backplane power is recognized by the module.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eThe module also provides diagnostics for loss of user-side power, helping maintenance personnel identify field power problems that may affect analog output operation.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eTechnical Specifications\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cfigure\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eIC200ALG320E\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGE Fanuc \/ Emerson\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Line\u003c\/td\u003e\n\u003ctd\u003eVersaMax\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003e4-Point Analog Current Output Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Outputs\u003c\/td\u003e\n\u003ctd\u003e4\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Configuration\u003c\/td\u003e\n\u003ctd\u003eSingle-ended, current-sourcing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Grouping\u003c\/td\u003e\n\u003ctd\u003eSingle group\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Signal\u003c\/td\u003e\n\u003ctd\u003e4-20 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAnalog Resolution\u003c\/td\u003e\n\u003ctd\u003e12 bits\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Resolution\u003c\/td\u003e\n\u003ctd\u003e4 uA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResolution\u003c\/td\u003e\n\u003ctd\u003e8 counts\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAccuracy (Full Scale)\u003c\/td\u003e\n\u003ctd\u003e0.3% typical; +\/-1% maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Update Rate\u003c\/td\u003e\n\u003ctd\u003e0.3 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eExternal Power Supply\u003c\/td\u003e\n\u003ctd\u003e18-30 VDC; 9.6-15 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNominal Supply Voltage\u003c\/td\u003e\n\u003ctd\u003e12 \/ 24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent Consumption\u003c\/td\u003e\n\u003ctd\u003e240 mA maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBackplane Current Draw\u003c\/td\u003e\n\u003ctd\u003e50 mA maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLED Indicators\u003c\/td\u003e\n\u003ctd\u003e2 (FLD PWR, OK)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDiagnostics\u003c\/td\u003e\n\u003ctd\u003eLoss of user-side power\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Default\u003c\/td\u003e\n\u003ctd\u003eHold last state or 4 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.94 lb\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003e\u003cstrong\u003eFrequently Asked Questions\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: How many analog output channels does the IC200ALG320E provide?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: It provides four single-ended analog current-sourcing channels. Each channel generates a 4-20 mA output signal and belongs to one output group.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What happens to the analog outputs if controller communication is interrupted?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The output behavior can be configured to hold the last output state or return to 4 mA. The selected setting determines the response to applicable controller, backplane, or communication interruptions.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What power supply does the IC200ALG320E require?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The module uses backplane power for its internal electronics and external field-side power for its analog output circuits. The supplied specifications list external supply ranges of 18-30 VDC and 9.6-15 VDC; verify the applicable wiring and supply configuration before installation.\u003c\/p\u003e","brand":"GE Fanuc","offers":[{"title":"Default Title","offer_id":69482476044530,"sku":"IC200ALG320E","price":352.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0730\/5589\/5794\/files\/IC200ALG320E.jpg?v=1795589290","url":"https:\/\/www.petrospare.com\/products\/ge-ic200alg320e-versamax-analog-current-output-module","provider":"Petro Spare Industrial Limited","version":"1.0","type":"link"}